This section explains how to maintain power monitoring devices (PDU or UPS).
Replacing power monitoring devices (PDU or UPS)
After replacing a power monitoring device, re-configure hardware properties of the power monitoring device (PDU or UPS).
Use the following procedure to replace a power monitoring device.
Replace the faulty power monitoring device.
Set the admin LAN IP address and SNMP community on the replacement device to the same values as those that were set on the faulty device.
Re-configure the power monitoring device's hardware properties.
In the ROR console server resource tree, right-click the target power monitoring device (PDU or UPS), and from the popup menu, select [Hardware Maintenance]-[Re-configure].
The [Re-configure Hardware Properties] dialog is displayed.
Click <OK>.
The target power monitoring device's hardware properties are re-configured.