This section explains how to change power monitoring environment settings.
Power environment settings include power monitoring device settings and collection settings.
Use the following procedure to change environmental data settings:
From the RC console menu, select [Tools]-[Options].
The [Options] dialog is displayed.
In the [Options] dialog, select the "Environmental Data" category title.
The "Environmental Data" area is displayed.
In the "Environmental Data" area, change the following items.
Select "Power", to start collecting power consumption data.
Enter the time interval of the data collection (1-6 or 10).
The number of devices that can be monitored simultaneously depends on the value of this polling interval and the load put on the admin server. The following values are guidelines.
Polling interval | Number of devices that can be monitored simultaneously |
---|---|
5 minutes | Up to 40 devices |
10 minutes | Up to 60 devices |
Use a polling interval of 5 minutes or longer when monitoring chassis and servers. Use a polling interval of 10 minutes if monitoring more than 40 devices.
Enter storage periods for each collection rate. Data older than the configured storage period will be deleted everyday.
Enlarging data storage periods reduces the number of devices that can be monitored simultaneously.
Use the default storage period values when monitoring chassis and servers.
Click <Apply>.
Note
If the "Power" checkbox under "Data to collect" is cleared, the collection of power consumption data (including the calculation of hourly, daily, and other summarized data) will not be performed anymore.
The following settings can be changed.
Device name
Admin LAN (IP address)
SNMP community
Voltage
Comment
Complete setting modifications on the actual power monitoring device before performing this procedure.
Use the following procedure to change power monitoring device settings:
From the RC console, right-click the power monitoring device tree, then select [Modify]-[Registration Settings] from the popup menu.
The [Modify Power Monitoring Device] dialog is displayed.
Edit the items to be changed in the [Modify Power Monitoring Device] dialog and click <OK>.